Model
|
PLUSⅡ-Pro
|
153
|
203
|
303 |
403 |
503 |
603 |
803 |
104 |
124 |
164 |
|
Capacity
|
VA/Watts
|
15KVA
12KW |
20KVA
16KW |
30KVA
24KW |
40KVA
32KW |
50KVA
40KW |
60KVA
48KW |
80KVA
64KW |
100KVA
80KW |
120KVA
96KW |
160KVA
128KW |
|
Input
|
Voltage
|
220Vac / 380Vac ±
20% (The different voltage specification is
available.)
|
|
Frequency
|
50
or 60 Hz ± 5%
|
|
Current
|
29A
|
39A
|
58A
|
77A
|
96A
|
116A
|
154A
|
193A
|
231A
|
308A
|
|
Max.
input current
|
41A
|
55A
|
82A
|
109A
|
136A
|
163A
|
218A
|
272A
|
326A
|
435A
|
|
Output
|
Voltage
|
220Vac / 380Vac ±
10% (The different voltage specification is
available.)
|
|
Phase
|
3ø4W+G
|
|
Waveform
|
Sinusoid
|
|
T.H.D.
|
≦3%
|
|
Voltage-Static
|
± 1%
|
|
Voltage-Dynamic
|
± 5%
|
|
Frequency
|
50 or 60 Hz ; ( ±0.01% with
internal oscillator ; ±1% with mains synchronize )
|
|
Indicator
|
LED
|
AC mains normal, reserve source
normal, rectifier, inverter, static switch, and battery status
indication
|
|
LCD
|
Inverter over-current shutdown,
inverter overload, rectifier high DC voltage stop, low battery stop,
over-temperature, fuse fail, and battery ground fault
Input voltage and frequency,
output voltage, current, and frequency, battery voltage and current,
and load level self-diagnosis wisely
|
|
Alarm
Buzzer
|
Buzzer
|
Load
on battery :
Discontinuous alarm
|
|
UPS abnormal :
Continuous
alarm
|
|
Remote
|
Monitor
|
Multi-unit monitor, graphic
display, and history data statistics
|
|
Control
|
Inverter/horns remote control,
password setting, fault information reading, and auto-dialer
|
|
Appearance
|
Weight
(kg)
|
380
|
420
|
490 |
550 |
670 |
750 |
900 |
1050 |
1200 |
1450 |
|
Size
W*D*H
|
600*800*1700
mm
|
800*800*1700
mm
|
1200*800*1700
mm |
|
Static
switch
|
Overload
current capacity
|
30 minutes: 120%
; 30 milliseconds: 1000%
|
|
Maximum
transfer time
|
From inverter to reserve─
a: inverter
failure: < 1msec ;
b: inverter
overload or manual operation: 0 msec
|
|
From reserve to inverter─
0msec
|
|
Complete
system
|
Overall
efficiency (at nominal load)
|
88%
|
89%
|
90%
|
91%
|
92%
|
|
Inverter
efficiency
|
90%
|
91%
|
92%
|
93%
|
94%
|
|
Inverter
overload
|
≦110%:15min
≦125%:10min
≦150%:60sec
|
|
Maximum
power dissipated (KW)
|
1.63
|
1.98
|
2.67
|
3.16
|
3.48
|
4.17
|
5.57
|
6.98
|
8.35
|
11.13
|
|
Audible
noise (at a distance of 1.5m)
|
≦60dBA
|
≦65dBA
|
|
Ambient
temperature
|
0~40ºC
|
|
Relative
humidity (no condensate)
|
90%
|
|
Interface
|
Communication
|
*
AS400 / RS232 / Dry Contact/EPO
* SNMP
Adapter (Optional)
|