Model
Plus-1000AR
Plus-2000AR
Plus-3000AR
Capacity
VA / Watts
1000VA/600W
2000VA/1200W
3000VA/1800W
Input Voltage
110/ 115/120Vac or 220/230/240Vac
Voltage Range
86Vac~ 144 Vac or 172Vac~288 Vac (+/-25%)
Frequency
47Hz~ 53Hz or 57Hz~63Hz
Output Voltage Regulation(Batt. Mode)
110/ 115/120Vac or 220/230/240Vac+/-10%
Frequency
50Hz or 60Hz +/-1Hz
Transfer Time
<6ms (typical)
Waveform
Simulated Sinewave
Europen type+IEC-320:
2+4
NEMA 5-15R:Battery/Surge only
6 / 2
Battery Battery Type
12V/7AH*2PC
12V/7AH*4PC
12V/9AH*4PC
Recharge Time
5 hours to 90% after complete discharge
User's Replacement
Yes
Battery Protection
Over discharge protection,short circuit protection by fuse
Advanced Battery Management
Yes
Battery Back-up Time
It depends on connecting loads and external battery packs
Function Display
LED display for line on, battery back up, AVR protection, load and battery level, overload and UPS cut off
Alarm
Buzzer on for Back-up mode,Battery low
Output Short Protection
AC fuse and electronic circuit(Line mode);electronic circuit (Back-up mode)
Communication Port
Shutdown software for Windows 95/98/NT/2000/ME/XP/Vista
Modem/Phone Protection
RJ-11/RJ-45
Lightning/Surge Protection
175 Joules
AVR (Auto. Voltage Regulation)
Boost / Buck
DC Start Function
Yes
Auto.Restart UPS
Yes
Over / Under Voltage Protection
Yes
Environment Safety Standard
CE (EN50091-1,EN62040-1-1)
EMC Standard FCC Part 15 Class B,CE (EN50091-2,EN55011,EN61000-3-2,EN61000-3-3)
Operating Temperature
0° ~ 40°C
Relative Humidity
0 ~ 95%, non-condensing
Audible Noise
<40 dBA at 1 meter
Physical Dimension(D*W*H)
530mm*19"*2U
Net Weight
21kgs
28kgs
31kgs
DESIGN, MANUFACTURE, SERVICES  
ISO 9001-2000
Warranty  
1 year

Copyright © Aplus Power Corp. 2002-2003, All Rights Reserved.